Program Example 1:
Communication between the ELC and MVX AC drives (ASCII Mode, M1143= OFF)
Program diagram
MOV
D1120
H87
M1002
SET
M1120
M1127
RST
M1127
Receiving
completed
Setting communication protocol 9600, 8, E, 1
Communication protocol latched
Setting communication timeout 100ms
Process of receiving data
Receiving completed and flag reset
Setting transmission flag
X1
X0
Setting communication command:
Data address H0706
Data H1770
Device address 01
The receiving data in ASCII character
format is stored in D1070~D1085
MOV
D1129
K100
SET
M1122
MODWR
H0706
K1
H1770
ELC
→
MVX, ELC transmits: “01 06 0706 1770 65 ”
MVX
→
ELC, ELC receives: “01 06 0706 1770 65 ”
ELC transmit message
Register
Data
Descriptions
D1089 low
‘0’
30 H
ADR 1
D1089 high
‘1’
31 H
ADR 0
ADR (1,0) is AC drive address
D1090 low
‘0’
30 H
CMD 1
D1090 high
‘6’
36 H
CMD 0
CMD (1,0) is instruction code
D1091 low
‘0’
30 H
D1091 high
‘7’
37 H
D1092 low
‘0’
30 H
D1092 high
‘6’
36 H
Data address
D1093 low
‘1’
31 H
D1093 high
‘7’
37 H
D1094 low
‘7’
37 H
D1094 high
‘0’
30 H
Data contents
D1095 low
‘6’
36 H
LRC CHK 1
D1095 high
‘5’
35 H
LRC CHK 0
LRC CHK (0,1) is error check
code
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...