E L C P r o g r a m m i n g M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003003E
3-182
4.
M10~ M13 = ON when the current value of C10 is equal to or greater than the lower-limit value
and equal to or less than the upper-limit value.
Lower-limit value
Upper-limit value
Current value of C10
Output
D100= 40
D101=100
40
≦
C10
≦
100
M10=ON
D102=120 D103=210
120
≦
C10
≦
210
M11=ON
D104=140 D105=170
140
≦
C10
≦
170
M12=ON
D106=150 D107=390
150
≦
C10
≦
390
M13=ON
5.
When the lower-limit value is greater than the upper-limit value, if the current value of C10 is
greater than the lower-limit value (C10>140) and less than the upper-limit value (C10<60),
M12=ON.
Lower-limit value
Upper-limit value
Current value of C10
Output
D100= 40
D101=100
40
≦
C10
≦
100
M10=ON
D102=120 D103=210
120
≦
C10
≦
210
M11=ON
D104=140 D105=
60
60
≦
C10
≦
140
M12=OFF
D106=150 D107=390
150
≦
C10
≦
390
M13=ON
400
200
0
40
100
120
210
60
140
150
390
M10
M11
M12
M13
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...