3 . I n s t r u c t i o n S e t
M N 0 5 0 0 3 0 0 3 E F or m o r e i nf o r m a t i o n v i s i t : www. e a t o n. c o m
3-479
MOV
MOV
MOV
K100
K100
K100
D0
M1002
D1131
D1343
D1348
SET
DMOV
K0
D1030
EI
FEND
IRET
END
DCLLM
X4
K50000 K100000
Y0
INC
M1534
M0
M1000
I401
MOV
K100
D1340
MOV
K100
D1343
MOV
K100
D1343
2. Execution
result:
100kHz
D1340
D1343
X4 = OFF --> ON
D1340
D1348
Specified number of output pulses: 50,000
Actual number of output pulses (D1030, D1031) = K51000
Frequency
Y0 output stops
Time
Pulse number
Program Example 4:
Immediate stop the high-speed pulse output with a high speed counter
1. C243 is used with an AB-phase input from the encoder. Set the target number of feedbacks =
50,000; target frequency = 100kHz; pulse output addresses: Y0, Y1 (CH0); start/end
frequency (D1340) = 100Hz; ramp-up time (D1343) = 100ms; ramp-down time (D1348) =
100ms; percentage value (D1131) = 100; present value of output pulses (D1030, D1031) = 0..
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...