EL C Pro g rammi ng Manu al
F O R MORE INFORM AT ION VISIT: WWW.E ATON.COM MN05003003E
2-56
2.14 Special Data Register
The special registers (special D) are as shown in the following. Please notice that some
equipments with the same number will be different to the different model. In the following chart, the
values in the “Type” column are: “R”: can only read. “R/W”: can read/write. A “-“ means it can do
nothing. “#” means this is a system setting. You can read the detailed explanation of the setting in
the manual.
Special D
Function
ELC
-PB
ELCB
-PB
ELC
-PC
-PA
-PH
ELCM
-PH
- PA
ELC
-PV
OFF
Ø
ON
STOP
Ø
RUN
RUN
Ø
STOP
Type Latched
Factory
setting
D1000
Watchdog timer (WDT) value (Unit:
1ms)
Y Y
Y Y
200
- - R/W NO 200
D1001
ELC program version (user can read
the ELC program version from this
register. For example, D1001 = H
XX10 means version 1.0
Y Y
Y Y
- - - R NO #
D1002
Program capacity
Y Y
Y Y
- - - R NO #
D1003
Sum of the ELC internal program
memory
Y Y
Y Y
- - - R NO #
D1004
Grammar detective number
Y Y
Y Y
0 0 - R NO 0
D1008
STEP address when WDT timer is ON
Y Y
Y Y
0 - - R NO 0
Number of LV signal occurrence
Y Y
Y -
D1009
Register for SRAM lost data error code
- -
- Y
0 - - R YES 0
D1010
Present scan time (Unit: 0.1ms)
Y Y
Y Y
0 0 0 R NO 0
D1011
Minimum scan time (Unit: 0.1ms)
Y Y
Y Y
0 0 0 R NO 0
D1012
Maximum scan time (Unit: 0.1ms)
Y Y
Y Y
0 0 0 R NO 0
D1015
0~32,767(unit: 0.1ms) addition type of
high-speed connection timer
- Y
Y Y
0 - - R/W NO 0
D1018
π
PI (Low byte)
- Y
Y Y 0FDB 0FDB 0FDB R/W NO 0FDB
D1019
π
PI (High byte)
- Y
Y Y 4049 4049 4049 R/W NO 4049
D1020
X0~X7 input filter (unit: ms)
0~1,000ms adjustable
Y Y
Y Y
10
- - R/W NO 10
ELC-PH: X10~X17 input delay times
setting (unit: Scan times)
- Y
- -
D1021
X10~X17 input filter (unit: ms)
Y -
- Y
0 - -
R/W
NO 0
D1022
Double frequency selection for AB
phase counter
Y Y
Y -
# - -
R/W
NO #
D1023
Storing detected pulse width (unit:
0.1ms)
Y Y
Y -
0 - -
R/W
NO 0
D1025
Communication error code
Y Y
Y Y
0 - - R NO 0
D1026*
Pulse number for masking Y0 when
M1156 = ON (Low word)
- -
Y Y
0 0 -
R/W
NO 0
D1027
Pulse number for masking Y0 when
M1156 = ON (High word)
- -
Y Y
0 0 -
R/W
NO 0
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...