E L C P r o g r a m m i n g M a n u a l
F o r
m o r e
i n f o r m a t i o n v i s i t :
w w w. e a t o n . c o m
M N 0 5 0 0 3 0 0 3 E
3 - 3 6 8
Register
Data
Descriptions
D1074 Low byte
‘0’
30 H
D1074 High byte
‘0’
30 H
D1075 Low byte
‘0’
30 H
D1075 High byte
‘2’
32 H
Number of Register
D1076 Low byte
‘E’
45 H
LRC CHK 1
D1076 High byte
‘1’
31 H
LRC CHK 0
z
RTU Mode: ELC connects to MVX drives
ELC
→
the drive, ELC transmits: 01 10 0705 0002 04 1770 0012 91 C2
The drive
→
ELC, ELC receives: 01 10 0705 0002 50 BD
ELC transmit data
Register
Data
Descriptions
D1256 Low byte
01 H
Address
D1257 Low byte
10 H
Function
D1258 Low byte
07 H
D1259 Low byte
05 H
Data Address
D1260 Low byte
00 H
D1261 Low byte
02 H
Number of Register
D1262 Low byte
04 H
Byte Count
D1263 Low byte
17 H
D1264 Low byte
70 H
Data
content 1
The content of register D50
(H1770=K6000)
D1265 Low byte
00 H
D1266 Low byte
12 H
Data
content 2
The content of register D51
(H12)
D1262 Low byte
91 H
CRC CHK Low
D1263 Low byte
C2 H
CRC CHK High
ELC receive data
Register
Data
Descriptions
D1070 Low byte
01 H
Address
D1071 Low byte
10 H
Function
D1072 Low byte
07 H
D1073 Low byte
05 H
Data Address
D1074 Low byte
00 H
D1075 Low byte
02 H
Number of Register
D1076 Low byte
50 H
CRC CHK Low
D1077 Low byte
BD H
CRC CHK High
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...