EL C Pro g rammi ng Manu al
F O R MORE INFORM AT ION VISIT: WWW.E ATON.COM MN05003003E
2-24
SM
Function
ELC
-PB
ELCB
-PB
ELC
-PC
-PA
-PH
ELCM
-PH
-PA
ELC
-PV
OFF
Ø
ON
STOP
Ø
RUN
RUN
Ø
STOP
Type Latched
Factory
setting
M1118
Deceleration flag (not available in ELC-
PH _VERSION 1.4 and above)
Y Y
- -
OFF OFF OFF R/W NO OFF
M1119
Completed function flag (not available in
ELC-PH_VERSION 1.4 and above)
Y Y
- -
OFF OFF OFF R/W NO OFF
M1120
Set COM2 (RS-485) protocol kept on.
D1120 cannot be changed after the
setting.
Y Y
Y Y
OFF OFF OFF R/W NO OFF
M1121 Transmission ready
Y Y
Y Y
OFF OFF
ON
R NO OFF
M1122 Sending request
Y Y
Y Y
OFF OFF OFF R/W NO OFF
M1123 Receiving completed
Y Y
Y Y
OFF OFF OFF R/W NO OFF
M1124 Receiving wait
Y Y
Y Y
OFF OFF OFF R/W NO OFF
M1125 Communication reset
Y Y
Y Y
OFF OFF OFF R/W NO OFF
M1126 STX/ETX user/system selection
Y Y
Y Y
OFF OFF OFF R/W NO OFF
M1127
MODRD/RDST/MODRW instructions.
Data receiving completed.
Y Y
Y Y
OFF OFF OFF R/W NO OFF
M1128 Transmitting/Receiving Indication
Y Y
Y Y
OFF OFF OFF R/W NO OFF
M1129 Receiving time out
Y Y
Y Y
OFF OFF
-
R/W NO OFF
M1130 STX/ETX selection
Y Y
Y Y
OFF OFF
-
R/W NO OFF
M1131
MODRD/RDST/MODRW, M1131=ON
when data convert to HEX
Y Y
Y Y
OFF OFF
- R NO OFF
M1132
ON= no relative communications
instruction in ELC program.
Y Y
Y Y
OFF
- - R NO OFF
M1133
Special high speed pulse (50KHz) output
switch (ON = start) (ELC-PC/PA)
Y10 outputs starting flag for two-axis
synchronous control (ELC-PH)
- Y
- -
OFF OFF OFF R/W
NO OFF
M1134
ON is continuous output switch (not
available in ELC-PH_VERSION 1.4 and
above)
- Y
- -
OFF OFF
-
R/W
NO OFF
M1135
Output pulse numbers attained flag (ELC-
PC/PA)
Y11 outputs starting flag for two-axis
synchronous control (ELC-PH)
- Y
- -
OFF OFF OFF R/W
NO OFF
M1136
For COM3(RS-485), retaining
communication setting
- - Y -
OFF
- -
R/W
NO OFF
M1137
Retain the data in DNET mapping area in
STOP state
- - - Y
- - -
R/W
NO OFF
M1138
Set COM1 (RS-232) protocol kept on.
D1036 cannot be changed after setting
Y Y
Y Y
OFF
- -
R/W NO OFF
COM1 (RS-232) ASCII/RTU mode
selections when ELC is a SLAVE (OFF in
ASCII mode and ON in RTU mode)
Y Y
Y Y
M1139 COM1 (RS-232) ASCII/RTU mode
selections when the ELC is a MASTER
(used with MODRD/ MODWR/MODRW
instructions) (OFF in ASCII mode and
ON in RTU mode)
- - Y -
OFF
- -
R/W
NO OFF
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...