E L C P r o g r a m m i n g M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003003E
3-102
API Mnemonic
Operands
Function
46
ANS
S, m, D
Alarm Set
Bit Devices
Word devices
Program Steps
Type
OP
X Y M S K H KnX
KnY
KnM KnS T
C D E
F
S
*
m
*
D *
ANS: 7 steps
ELC ELCB
ELCM
PB PC/PA/PH
PV
PB PH/PA
32 16
P
32 16
P
32 16
P
32 16 P 32 16 P
Operands:
S
: Alarm timer
m
: Time setting prior to alarm
D
: Alarm
Description:
1.
ANS instruction is used to drive the output alarm device.
2. ELC-PC/PA/PH:
Operand
S
valid range: T0~T191
ELC-PV: Operand
S
valid range: T0~T199
ELCM-PH/PA: Operand
S
valid range: T0~T183
Operand
m
valid range: K1~K32,767 in units of 100 ms
ELC-PC/PA/PH: Operand
D
valid range: S896~S1023
ELC-PV: Operand
D
valid range: S900~S1023
ELCM-PH/PA: Operand
D
valid range: S912~S1023
3.
See ANR for more information
4.
Flag: M1048 (ON = Alarm Active), M1049 (ON = Enable Alarms)
Program Example:
If alarm device S999=ON and X3 = ON for more than 5 seconds, S999 will stay ON after X3=OFF.
T10 will be reset to OFF, present value=0)
X3
ANS
T10
K50
S999
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...