3 - 3 5 9
Data received
Register
Data
Descriptions
D1070 Low byte
‘0’
30 H
ADR 1
D1070 High byte
‘1’
31 H
ADR 0
D1071 Low byte
‘0’
30 H
CMD 1
D1071 High byte
‘6’
36 H
CMD 0
D1072 Low byte
‘0’
30 H
D1072 High byte
‘7’
37 H
D1073 Low byte
‘0’
30 H
D1073 High byte
‘6’
36 H
Data Address
D1074 Low byte
‘1’
31 H
D1074 High byte
‘7’
37 H
D1075 Low byte
‘7’
37 H
D1075 High byte
‘0’
30 H
Data content
D1076 Low byte
‘6’
36 H
LRC CHK 1
D1076 High byte
‘5’
35 H
LRC CHK 0
z
RTU Mode (M1143=ON): ELC connects to the drive
ELC
→
the drive, ELC transmits: 01 06 0706 1770 66 AB
The drive
→
ELC, ELC receives: 01 06 0706 1770 66 AB
ELC transmit data
Register
Data
Descriptions
D1256 Low byte
01 H
Address
D1257 Low byte
06 H
Function
D1258 Low byte
07 H
D1259 Low byte
06 H
Data Address
D1260 Low byte
17 H
D1261 Low byte
70 H
Data
content
The content of register D50
(H1770=K6000)
D1262 Low byte
66 H
CRC CHK Low
D1263 Low byte
AB H
CRC CHK High
Data received
Register
Data
Descriptions
D1070 Low byte
01 H
Address
D1071 Low byte
06 H
Function
D1072 Low byte
07 H
D1073 Low byte
06 H
Data Address
D1074 Low byte
17 H
D1075 Low byte
70 H
Data content
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...