E L C P r o g r a m m i n g M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003003E
3-128
Applicable Hardware High Speed Counters:
1-phase
input
1-phase 2-input
2-phase 2-input
C
X
C243 C244 C245 C246 C247 C248 C249 C250 C251 C252 C253 C254
X0 U
U/D
U/D
U
U A
A
X1 R
Dir
Dir
D
D B
B
X2 U
U/D
U/D
A
A
X3 R
Dir
Dir
B
B
X4 R R R
X5
R
R
U: Count up
A: Phase A input Dir:
Direction
signal
input
D: Count down
B: Phase B input
R: Reset signal input
Note:
a) The max. frequency of the 1-phase input X0 (C243, C245, C246) and X2(C242) is
100kHz.
b) The max. frequency of the 1-phase 2-input (X0, X1) (C245, C246) and (X2, X3) (C249,
C250) is 100kHz.
c) The max. frequency of the 1-phase 2-input (X0, X1) (C247, C248) is 10kHz.
d) The max. frequency of the 2-phase 2-input (X0, X1) (C251, C252) and (X2, X3) (C253,
C254) is 5kHz.
e) 2-phase 2-input counting supports double and 4 times frequency, which is selected in
D1022 as the table in next page. Please refer to the below table for detailed counting
wave form.
D1022
Counting mode
K2
(Double Frequency)
A
B
up co
unt
down c
ount
A
B
up co
unt
down c
ount
K4 or other value
(4 times frequency)
(Default)
A
B
up
cou
nt
dow
n co
unt
A
B
up
cou
nt
dow
n co
unt
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...