background image

Nord GSM / Nord GSM WRL

Operation manual

October 12, 2018

Summary of Contents for GSM

Page 1: ...Nord GSM Nord GSM WRL Operation manual October 12 2018...

Page 2: ...ation 11 2 1 5 Standby Mode Indication 11 2 2 K14 LED Keypad 12 2 2 1 Getting Information about Site Status 13 2 2 2 Getting Information about Partition Status 13 2 2 3 Arming and Disarming 13 2 2 4 S...

Page 3: ...r EW 12 30 3 6 Connection of Expander EW 8 34 3 7 GSM Channel Setting 35 3 7 1 SIM Card Installation 35 3 7 2 Check of GSM Signal Level 36 3 7 3 Connection of Remote GSM Antenna 36 3 8 Connection of T...

Page 4: ...GPRS Transmission Parameters 70 5 8 3 Transmission Parameters over Ethernet 71 5 8 4 Transmission Parameters in GSM CSD Channel 72 5 8 5 Transmission Parameters via GSM voice channel 72 5 8 6 SMS Tran...

Page 5: ...gineer 89 6 2 2 Granting Permissions to Engineer 91 6 3 Device Remote Configuration 91 6 3 1 Selection of Site to Configure 91 6 3 2 Working with Configuration 92 6 3 3 Work Features 93 6 4 Remote Sof...

Page 6: ...to the connected communication modules communicators and devices for expanding its functionality within the limits of permissible consumed capacities 1 2 Power Supply The main power source of the pro...

Page 7: ...connected to the dedicated socket of the product main board via the radio channel in the midband VHF UHF bands with the help of an optional radio transmitter connected to the interface connector TR 1...

Page 8: ...o channel terminal units can be used manual security detector CN KeyFob volume electro optical security detector CN PIR volume electro optical street security detector CN PIR Outdoor manual security d...

Page 9: ...load current of discrete outputs is 500 mA the maximum permissible DC voltage supplied to the outputs is plus 50 V The main board is equipped with a multifunctional three color process LED designed to...

Page 10: ...he product is marked in the form of labels with the name of the product and bar code The labels are glued on the front side of the product printed circuit board and case In addition the label is glued...

Page 11: ...or disarm one partition If one user has to be able to arm or disarm several partitions at the same time then the appropriate rules shall be set in the Automatic controls section 2 1 1 Reading Indicat...

Page 12: ...re configured in the device then the indication after the current one is armed depends on whether the disarmed partitions remained or not If all partitions are armed the LED turns on and remains lit t...

Page 13: ...that the LED turns on for 1 second then turns off for 1 second then turns on again for 1 second etc Several Partitions If several partitions are configured in the device then only the following is in...

Page 14: ...d some of them are armed and others are disarmed the keypad displays an error indication if the partitions are not configured on the device the keypad displays an error indication 2 2 2 Getting Inform...

Page 15: ...essary to enter the user code if the code is correct then the site partition will be disarmed The keypad will confirm disarming by turning on the green LED if the code is incorrect or the user who own...

Page 16: ...pressed The keypad has a volume control for the built in speaker The Adjustment is five step from the state off to the volume levels from the first to the fourth The volume level can be selected by p...

Page 17: ...e device has the ability to arm and disarm several partitions with one user code The partitions that can be armed or disarmed with a specific code are configured during the device configuration Arming...

Page 18: ...which state shall be changed then such code is treated as incorrect Arming Rejection Arming rejection is the impossibility to arm the site if the security alarm on the site is faulty or arming is pro...

Page 19: ...he current status of the device as well as on operations performed by the user Standby indication the device is completely disarmed If all partitions of the device are disarmed and users do not perfor...

Page 20: ...med If the device is fully armed and the user does not perform any operations with the keypad the current time information that the device is fully armed are displayed on the keypad screen Example of...

Page 21: ...g a reason for which arming is impossible is detected the information on the arming rejection and the reason are displayed on the keypad screen In addition to indicate the arming rejection the sound i...

Page 22: ...ower up the keypad is powered by two lithium batteries type CR123A main and backup To replace the batteries it is necessary to open the battery cover of the keypad install the backup battery first and...

Page 23: ...e user code if the code is correct then the site partition will be armed the keypad will confirm the arming by turning on the red LED Or the countdown of the exit delay will start which will be accomp...

Page 24: ...igure 12 If the user can control several partitions to disarm them it is necessary to type the partition number then and enter the user code If the code is correct then the partition will be disarmed...

Page 25: ...d as a panic button then the keypad will display an error 2 4 4 Backlight and Sound Turning Off CN Keypad can turn on and off the sound and backlight To turn on or turn off the sound confirmation of p...

Page 26: ...3 Installation and First Start 3 1 Device Wiring Diagram Figure 14 25...

Page 27: ...e zone in parallel and normally closed in series One zone can include detectors of only one type either normally closed or normally open 3 2 2 Terminating Resistors If the terminating resistors are no...

Page 28: ...ure 16 Normally closed zone 3 2 4 Zone with One Terminating Resistor Figure 17 Normally open zone Figure 18 Normally closed zone 3 2 5 Zone with Two Terminating Resistors Figure 19 Normally open zone...

Page 29: ...sed zone 3 2 6 Wired Zones in Configurator When configuring the device it is necessary to explicitly specify the rate for the wired zone and the number of terminating resistors It is possible to do th...

Page 30: ...terminal In this case after the alarm repetition interval is over see section Configuration the power supply from the detectors will be switched off for a short time If resetting the power of the fire...

Page 31: ...rature sensor it is necessary to turn on the mode of constant polling of the 1 Wire interface in the device settings It is possible to do this on the Miscellaneous tab in the Control and indication se...

Page 32: ...to the device via group of terminals Reader which is located on the left edge of the device terminals the 1WR terminal of the expander is connected to the DATA terminal of the device and the 1WR GND t...

Page 33: ...12V Power can be supplied in two ways From the device itself it shall be noted that the maximum load is 200 mA From an uninterruptible power source Connection of Zones to Expander Terminals Z1 Z8 are...

Page 34: ...in the Connection of Wired Zones section Each of terminals Z1 Z8 can be a zone or an open collector output which is indicated when configuring the control panel If the zone is disabled in the configu...

Page 35: ...3 6 Connection of Expander EW 8 Figure 26 Diagram of EW 8 connection to device 34...

Page 36: ...on SIM2 is on top SIM cards are installed in the holder with the contact pad towards the board Before installing SIM cards in the device completely disconnect it otherwise the SIM card can be disabled...

Page 37: ...internal antenna with a remote antenna check that the board with the installed remote antenna fits tightly to the posts if necessary drill a 10 mm hole in the body to bring the antenna feeder out In...

Page 38: ...s Touch Memory protocol emulation DS1990A For example Proximity readers PS 01 CP Z2B It shall be taken into account that to connect some readers that emulate the DS1990A protocol it is necessary to di...

Page 39: ...software version of the device The package for updating the software version of the device includes the latest firmware versions for the following devices Nord GSM Nord GSM WRL Nord LAN Nord RF Nord G...

Page 40: ...Figure 30 Figure 31 Right click on the Soyuz CDC device and select the menu item Update drivers 39...

Page 41: ...eject the proposal to automatically find the driver for the new hardware select the driver installation manually Figure 33 Selection of manual installation Specify the path to the Driver folder and cl...

Page 42: ...device does not have a digital signature Therefore you shall explicitly confirm to the operating system the need to install it Figure 35 Confirming the driver installation without a digital signature...

Page 43: ...tion To make sure that the driver for the device is installed open the Windows Device Manager and find the virtual serial port that corresponds to the device connected to the computer Figure 37 Device...

Page 44: ...ry check of driver signature disabled To download the Windows 8 operating system with driver verification disabled perform the following sequence of steps Press the key combination Win I then hold the...

Page 45: ...ure 40 Advanced diagnostics parameters In the Additional parameters window select Boot parameters Figure 41 Operating system boot parameters In the Boot parameters window left click the Reboot button...

Page 46: ...oading the operating system with driver signature verification disabled Figure 43 Disabling mandatory driver signature verification After the operating system starts install the device driver in the s...

Page 47: ...n of the software that is installed on it Figure 44 Display of software version on the device If the software version on the device is smaller than the version of the update it is necessary to update...

Page 48: ...r updating the firmware via USB can be closed If an error message appears during the update process it is recommended to disconnect the device from the computer close the utility for updating the firm...

Page 49: ...quently used programs After the configurator is started it automatically detects the device connected to the computer checks the software version installed on the device and loads the device settings...

Page 50: ...splayed in the configurator Use the Open button to load the settings from the file To avoid errors related to setting up communication channels it is recommended to save all settings related to connec...

Page 51: ...ia GSM and Ethernet communication channels can be specified on the Security Center tab Parameters that determine the transmission of events over a radio channel are spec ified on the Radio tab The Clo...

Page 52: ...o the device additional zones will appear automatically in the configurator Operation details and connection diagram of the expander to the device are given in section Connection of EW 12 Expander EW...

Page 53: ...one is disabled it cannot be added to the part it is not displayed in the list of zones available for adding to the part The zone disabling can be useful in case it is necessary to temporarily stop th...

Page 54: ...ype If the zone type is set to Bypass then this zone is specially handled during arming and disarming When arming the bypass zone state is ignored the device will be armed even if the zone configured...

Page 55: ...e zone cable in any accessible location and the zone will remain in the normal state forever there will never be any alarms on such a zone The zone which normal state is defined as closed does not loo...

Page 56: ...ded in the part if a faulty cable is detected the device refuses to arm if the alarm zone is detected the device also refuses to arm if there are no faulty or alarm zones the device is armed and the e...

Page 57: ...vice connection CN Siren To connect devices such as CN Siren and CN Smoke it is necessary to Remove the front cover install the batteries Click the button Add Wireless Device on the Wireless devices t...

Page 58: ...a ventilation duct behind the wall from the installation site of the panel that prevents the passage of the signal 2 To slightly improve the parameters of the radio path it is possible to straighten t...

Page 59: ...the site Figure 53 Users tab code entry dialog To add a Touch Memory key click the Scan button in the Keys column then attach the TM key to the reader If the reader is connected correctly the key cod...

Page 60: ...pecific user using the Add keyfob button Connect the wireless keyfob to the device on the Wireless devices tab After the keyfob is added it is possible to go to the Partitions and match the keyfob wit...

Page 61: ...uring the partition arming or disarming the user shall be mapped to this partition To do this click the Add code button and select those users from the drop down list who will be able to manage a part...

Page 62: ...rm in another zone then such an alarm will be transmitted to the repeater and a countdown of its own alarm repetition interval will begin for this zone If the Interval for repeating alarms parameter i...

Page 63: ...ransmitted by the same wireless detector In this case in contrast to the repetition intervals of repetition of security or fire alarms the interval for repeating faults stops if a recovery of the faul...

Page 64: ...ify the interval during which the audit system is waiting for the event to be sent The audit system is a program mechanism that controls the fact of the event transfer to the receiver If the Interval...

Page 65: ...lectors FIRE DEFECT LED G LED Y FIRE2 DEFECT2 DISABL After connecting the siren the output shall be configured using the automation rules See more about the rules in the partition Automatic controls s...

Page 66: ...want to be sure that all alarm zones are normal at the time of arming it is possible to enable alarm monitoring in zones with exit delay To do this check the Disable arming when triggering the alarm...

Page 67: ...containing 6 numbers To use six digit codes for arming and disarming first it is necessary to set this parameter and then create users If the device already has users with a four digit code first it i...

Page 68: ...ding zones users partitions etc and the password for connecting to the device via USB will be default Enable restore of factory defaults The reset function can be enabled or disabled for a specific de...

Page 69: ...connecting over Ethernet station format for radio transmission Before saving the configuration the device issues a warning Figure 67 Miscellaneous tab Configuration protection section warning about e...

Page 70: ...ion stage This serial number can be transmitted to the receiver and serve as an alternative to the site number when identifying the device The Transmit device identifier to remote program parameter is...

Page 71: ...th pairs address port are valid for both SIMs installed in the device irrespective of which SIM is currently active the device will first attempt to connect to the receiver with the parameters Address...

Page 72: ...the DNS name and IP address is also specified by the security company What happens if for some reason it is necessary to cancel the contract with the carrier which gives the security company access t...

Page 73: ...d for the currently active SIM and if the transmission of the event fails then it dials the second one If only one modem is installed on the receiver to receive events via CSD then the second phone nu...

Page 74: ...hannel in the Security Center software it is necessary to use GSM Events Source This source of events can be added or it can be changed in the Event manager module Any GSM modem which command system i...

Page 75: ...hannel switching The order of switching IP channels in the absence of events is shown in the figure with blue dashed lines Black solid lines show the scheme for switching all configured channels when...

Page 76: ...anufacturer at the station delivery and is specified in its accompanying documentation Since there is no acknowledgment of event reception from the station when transmitting by radio the site device t...

Page 77: ...from the service events formed by the device and in addition from the events formed by another partition 5 9 3 Device in metal case If it is assumed that the control panel will work by radio then it i...

Page 78: ...then click the Private Cloud button and then enter the pin code which you received when configuring your Private Cloud Figure 81 Cloud tab Private Cloud is selected If the Private Cloud server pin is...

Page 79: ...re set individually for each device Figure 84 Ethernet tab reception of settings from the DHCP server is enabled Besides if the network to which the device is connected does not have a DHCP server tha...

Page 80: ...mon carriers Before starting the device via GSM it is important to make sure that the parameters of the SIM card used in the device are indicated If there are no parameters for the selected carrier in...

Page 81: ...he annunciators are connected it is necessary to use the buttons Light indicator or Siren depending on the type of the annunciator When creating rules it is important to remember the following If the...

Page 82: ...e output to which the annunciator is connected In the event that several partitions are configured on the device then when creating the rule it is possible to specify the partition for which the light...

Page 83: ...voltage of 12 V can be connected to the devices The maximum current shall not exceed 250 mA Rule setting For siren it is necessary to set up a rule with the role of Siren To create a rule in the Auto...

Page 84: ...action that arms the partition on a schedule 1 On the Automatic controls tab click the Miscellaneous button 2 In the Action field from the drop down list select the Arming 3 In the Partition field sel...

Page 85: ...f the discrete outputs of the device It is possible to configure arming of all site partitions using the All partitions value of the Partition field To configure the arming of several specific partiti...

Page 86: ...tted to the receiver text description of the event the number of the site for which the event was generated partition number zone or user number information about the current state of the event column...

Page 87: ...active whether there is connection to the Security Center and Cloud what errors occurred when the channel was initialized connected to the receiver or transmitted events Click the On button to force...

Page 88: ...re is any malfunction this will be indicated at the bottom of the icon By clicking on the wireless device icon it is possible to get more detailed information about its status Evaluation of wireless d...

Page 89: ...the Cloud via CML protocol using streaming encryption CML protocol C Nord Markup Language developed by C Nord company The alarm monitoring software is also connected to the Cloud via the encrypted pro...

Page 90: ...ile application events by sites for operation of the personal account and mobile applications Cloud transmits the following to the alarm monitoring software events about engineer s attempts to connect...

Page 91: ...lue of this field If the engineer for whom the account is created shall be able to remotely update the software on devices that are installed on the sites check the box Allow an engineer to remotely u...

Page 92: ...engineer who needs remote access to the site Figure 103 6 Specify the time interval during which the permission will be valid 7 Click the Give permission button 6 3 Device Remote Configuration Import...

Page 93: ...figuration is read Then it is possible to make the necessary changes and write them to the device with the corresponding button After a successful download of the configuration the message Settings sa...

Page 94: ...If during the remote configuration by one engineer another engineer will change the device settings locally using the desktop configurator it will be impossible to apply remote settings the configurat...

Page 95: ...vice is connected Downloading Current Firmware Once the device has received the update command it starts downloading the archive with the current software version The total file size is from 200 to 50...

Page 96: ...te Figure 109 And click the Update button After that this site will be added to the queue for software update 6 4 4 Updating Software on all Sites After checking the software on several sites it is po...

Page 97: ...ocess Stopping If for some reason there is a need to stop the update process it can be interrupted until the device has completely downloaded the update file To do this click Cancel update and confirm...

Page 98: ...09 RW Fault Faulty battery E311 RW Fault Disconnected battery E314 HK LB Fault Fault of wireless device main battery or fire zone power supply connected via EFW 2 E321 SC Fault Faulty siren E331 HK LB...

Page 99: ...tion with CN WRL R110 DS HJ Reset Fire alarm R118 DS HJ Reset Danger of fire R120 DS HJ Reset Panic button R130 DS HJ Reset Armed zone R133 DS HJ Reset 24 hour armed zone R137 RT Reset Closed device c...

Page 100: ...pen discrete output R752 System Reset of parameter values is cancelled R753 System Restart for an unknown reason R754 System Restart by audit system command R755 System Discrete output is opening clos...

Reviews: