A H 5 0 0 M o t i o n C o n t r o l M o d u l e M a n u a l
Sourcing
Direct current
Current flows from the common terminal S/S.
Equivalent circuit of the input circuit
S/S
X0.8
I/O
Internal
circuit
Wiring differential input terminals
The direct-current signals ranging in voltage from 5 V to 24 V can pass through the high-speed input
terminals X0.8+~X0.15+, and X0.8-~X0.15- on AH20MC-5A. The frequency of input signals can be
up to 200 kHz. These high-speed input terminals are connected to a differential (two-wire) line
driver.
The wiring of the differential input terminals are shown below. (The wiring is used for high speed and
noise):
AH20MC-5A high-speed input
Encoder output
A-
X0.8+
X0.8-
A+
A
B-
X0.9+
X0.9-
B+
B