Chapter 3 Site Planning and Preparation
Installation and Commissioning Manual
71
F
S
P
3000R
7 R
11
.1 8000
0015930
Issue
B
, ©
2012
ADVA AG Optical Netw
orking
ADVA Conf
idential
and its proximity to the PDU power connectors. Therefore DC power cables of
different lengths are required.
AC Power Cables
To connect a PSU/7HU-AC to line power, use a detachable, flexible AC power
cable with suitable electric and insulation ratings in accordance with your local
safety standards. The power cable and the assembled connectors must bear
the safety agency certification mark for the specific region or country intended
for installation.
The AC power cables must comply with the minimum requirements described in
. For detailed information about the power cables, please refer
to the
Hardware Description
and
Module and System Specification
.
P
S
Note
DC power cables fitted with ring lugs on one end are available to be
delivered with the equipment, but you must order them separately.
For information about placing an order, contact ADVA Optical
Networking. Information about these power cables can be found in
the
Hardware Description
,
Appendix A: DC Power Cables
. As the
customer, you are responsible for assembling the appropriate
terminal connectors at the wiring end that is attached to the external
DC power source.
Table 7: AC Power Cable Minimum Requirements
Region
Approvals
Number of
Conductors
Min.
Wire
Size
Temperature
Rating
Supply End
Equipment
End
North America UL Listed,
CSA
certified
3 18
AWG
flexible
105°C
(221°F)
min. VW-1,
SVT type
plug types:
18/3 SVT,
NEMA 5-15P,
NEMA 6-20P,
L, N, PE pins
plug rating:
125 VAC, 10 A
female AC
appliance
coupler
according
to IEC/EN
60320-
C13
Continental
Europe
VDE
certified,
European
3
H05W-F
1.5 mm
2
flexible
105°C
(221°F)
plug type:
CEE 7/7,
CEE 7/4,
L, N, PE pins,
plug rating:
250 VAC, 10 A
International
UL Listed,
VDE
certified or
harmonized
3
1.5 mm
2
flexible
acc. to local
and national
electrical
codes with L,
N, PE pins,
plug rating:
250 VAC, 10 A