Installing the FSP 3000R7 ROADM-C40/40/OPM-3HU/2DC Shelf
218
Installation and Commissioning Manual
F
S
P
3000R
7 R
11
.1 8000
0015930
Issue
B
, ©
2012
ADVA AG Optical Netw
orking
ADVA Conf
idential
End of Procedure
Earthing the ROADM-C40/40/OPM-3HU/2DC Shelf
Earthing the ROADM-C40/40/OPM-3HU/2DC shelf is fulfilled by installing a
10-gauge earthing conductor from each shelf to an earth point connector on the
rack. Follow the procedure below to earth the ROADM-C40/40/OPM-3HU/2DC
shelf.
Procedure
Step 1
Mount the supplied 10-gauge green earthing wire with the two-hole
lug to one set of the dual threaded posts on the
ROADM-C40/40/OPM-3HU/2DC. Use the supplied nuts and star
washers as shown in
P
S
Note
One extra mounting screw is normally shipped with each shelf. If you
have a screw left over at this stage, discard it or store it for future use.
P
S
Note
The shelves shall reliably and permanently be connected to the earth
point of the rack.
P
S
Note
Earthing (grounding) regulations may differ considerably among
countries.