6.12 Diagnosis with the Online Monitor (OLM)
507
6.12.11 Frequent Causes of Error
Servo drive cannot
be switched on
The servo drive cannot be switched on or does not move:
1
Check whether the drive was enabled by the CC.
Select: Login Ipo/Axes/Ipo Act State 1:
Activated
()
Activated=false: Presumably an error on the CC or a hardware problem
2
Check whether “Drive on” was requested by the PLC.
Select: Login Ipo/Axes/Plc Nom State:
DriveOnReq
()
DriveOnReq=false: Presumably an error in the PLC program
3
Check whether the drive was switched on.
Select: Login Ipo/Axes/Ipo Act State 1:
DriveOn
()
DriveOn=false: Presumably an IPO-internal error
4
Check whether position feedback control was requested by the PLC.
Select: Login Ipo/Axes/Plc Nom State:
PosCtrlRequest
PosCtrlRequest=false: Presumably an error in the PLC program
5
Check whether position feedback control is active.
Select: Login Ipo/Axes/Ipo Act State 1:
PosCtrlActive
6
Check whether “feed rate enable” was set by the PLC.
Select: Login Ipo/Axes/Plc Nom State:
NoFeedHold
Summary of Contents for MILLPWR G2
Page 1: ...Technical Manual ACU RITE MILLPWRG2 ...
Page 2: ......
Page 14: ...14 ACU RITE Technical Manual MILLPWRG2 ...
Page 40: ...40 ACU RITE Technical Manual MILLPWRG2 ...
Page 58: ...58 ACU RITE Technical Manual MILLPWRG2 3 10 3 USB Hub ...
Page 60: ...60 ACU RITE Technical Manual MILLPWRG2 TS 220 Adapter cable for TS 120 TS 220 ...
Page 61: ...3 10 Dimensions 61 SE 640 transmitter receiver unit ...
Page 62: ...62 ACU RITE Technical Manual MILLPWRG2 SE 540 transmitter receiver unit ...
Page 63: ...3 10 Dimensions 63 TS 440 TS 640 ...
Page 64: ...64 ACU RITE Technical Manual MILLPWRG2 ...
Page 392: ...392 ACU RITE Technical Manual MILLPWRG2 ...
Page 545: ......