5.15 Integrated Oscilloscope
381
In the dialog box, set:
Type of display:
Set the time interval for recording the signals.
• YT: Chronological depiction of the channels
• YX: Graph of two channels
• Circle: Circular plot of two channels
Sampling time:
Set the time interval for recording the signals.
• CC clock: Time interval = 0.6 ms
• IPO clock: Time interval = IPO clock
(from MP_System/CfgCycleTimes/ipoCycle)
• PLC clock: Time interval = PLC clock
(results from MP_System/CfgCycleTimes/plcCount * Ipo clock)
3000 grid points (events) are stored. The time grid determines the duration of
recording.
Examples:
0.6 ms
⋅
3000 = 1.8 s
3 ms
⋅
3000 = 9 s
21 ms
⋅
3000 = 63 s
Channel 1 to channel 6
Specify the signals to be recorded:
Assign the channels of the analog signals to be recorded to the respective
axes.
Specify the operand type (B,W,D,I,O,T,C) and the address for the recording
of PLC operands
Use the
SAVED
setting to “freeze” the signal last recorded for this channel.
This means that the recorded values remain available on the display. For
example, you can use them to record a reference curve for use in future
measurements.
Summary of Contents for MILLPWR G2
Page 1: ...Technical Manual ACU RITE MILLPWRG2 ...
Page 2: ......
Page 14: ...14 ACU RITE Technical Manual MILLPWRG2 ...
Page 40: ...40 ACU RITE Technical Manual MILLPWRG2 ...
Page 58: ...58 ACU RITE Technical Manual MILLPWRG2 3 10 3 USB Hub ...
Page 60: ...60 ACU RITE Technical Manual MILLPWRG2 TS 220 Adapter cable for TS 120 TS 220 ...
Page 61: ...3 10 Dimensions 61 SE 640 transmitter receiver unit ...
Page 62: ...62 ACU RITE Technical Manual MILLPWRG2 SE 540 transmitter receiver unit ...
Page 63: ...3 10 Dimensions 63 TS 440 TS 640 ...
Page 64: ...64 ACU RITE Technical Manual MILLPWRG2 ...
Page 392: ...392 ACU RITE Technical Manual MILLPWRG2 ...
Page 545: ......