Table 25: Basic parameters G2.1
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.1.10 *
Motor cos phi
0.30
1.00
0.85
120
Find the value on
the rating plate of
the motor.
P2.1.11 *
I/O reference
0
3
1
117
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.1.12 *
Keypad control
reference
0
3
2
121
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.1.13 *
Fieldbus control
reference
0
3
3
122
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.1.14
Jogging speed ref.
0.00
P2.1.2
Hz
0.00
124
P2.1.15
Preset speed 1
0.00
P2.1.2
Hz
5.00
105
Speeds preset by
operator.
P2.1.16
Preset speed 2
0.00
P2.1.2
Hz
10.00
106
Speeds preset by
operator.
P2.1.17
Preset speed 3
0.00
P2.1.2
Hz
12.50
126
Speeds preset by
operator.
P2.1.18
Preset speed 4
0.00
P2.1.2
Hz
15.00
127
Speeds preset by
operator.
P2.1.19
Preset speed 5
0.00
P2.1.2
Hz
17.50
128
Speeds preset by
operator.
P2.1.20
Preset speed 6
0.00
P2.1.2
Hz
20.00
129
Speeds preset by
operator.
P2.1.21
Preset speed 7
0.00
P2.1.2
Hz
22.50
130
Speeds preset by
operator.
P2.1.22
Preset speed 8
0.00
P2.1.2
Hz
25.00
133
Speeds preset by
operator.
P2.1.23
Preset speed 9
0.00
P2.1.2
Hz
27.50
134
Speeds preset by
operator.
P2.1.24
Preset speed 10
0.00
P2.1.2
Hz
30.00
135
Speeds preset by
operator.
MULTI-STEP SPEED CONTROL APPLICATION
VACON · 75
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
4
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......