Table 2: Basic parameters G2.1
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.10
Motor cos phi
0.30
1.00
0.85
120
Find the value on
the rating plate of
the motor.
P2.11
Start function
0
2
0
505
0 = Ramp
1 = Flying start
2 = Conditional fly-
ing start
P2.12
Stop function
0
3
0
506
0 = Costing
1 = Ramp
2 = Ramp + Run
enable coast
3 = Coast + Run
enable ramp
P2.13
U/f optimisation
0
1
0
109
0 = Not used
1 = Automatic tor-
que boost
P2.14
I/O reference
0
3
0
117
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.15
Analogue input 2,
reference offset
0
1
1
302
0 = 0-20 mA
1 = 4 mA-20mA
P2.16
Analogue output
function
0
8
1
307
0 = Not used
1 = Output freq. (0-
f
max
)
2 = Freq. refer-
ence (0-f
max
)
3 = Motor speed
(0-Motor nominal
speed)
4 = Output current
(0-I
nMotor
)
5 = Motor torque
(0-T
nMotor
)
6 = Motor power
(0-P
nMotor
)
7 = Motor voltage
(0-U
nMotor
)
8 = DC-link volt
(0-1000V)
VACON · 16