Table 73: NXP drives: Closed Loop parameters (Control keypad: Menu M2 ->G2.6.23)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.6.23.17 Current control P
gain
0.00
320.00
%
40.00
617
Gain for the cur-
rent controller.
This controller is
active only in
closed loop and
advanced open
loop. It generates
the voltage vector
reference to the
modulator.
P2.6.23.18
CurrentControl-
Time
0.0
3200.0
ms
1.5
657
Current controller
integrator time
constant (0-1000) =
0-100.0 ms.
P2.6.23.19 Generator power
limit
0.0
300.0
%
300.0
1290
The maximum
power limit of the
generating side.
P2.6.23.20
Motoring power
limit
0.0
300.0
%
300.0
1289
The maximum
power limit of the
motoring side.
P2.6.23.21
Negative torque
limit
0.0
300.0
%
300.0
645
P2.6.23.22
Positive torque
limit
0.0
300.0
%
300.0
646
P2.6.23.23
Flux off delay
-1
32000
s
0
1402
-1 = Always
P2.6.23.24
Stop state flux
0.0
150.00
%
100.00
1401
P2.6.23.25
SPC f1 point
0.00
320.00
Hz
0.00
1301
P2.6.23.26
SPC f0 point
0.00
320.0
Hz
0.00
1300
P2.6.23.27
SPC Kp f0
0
1000
%
100
1299
P2.6.23.28
SPC Kp FWP
0
1000
%
100
1298
P2.6.23.29 SPC torque mini-
mum
0.0
400.0
%
0.0
1296
P2.6.23.30 SPC torque mini-
mum Kp
0
1000
%
100
1295
P2.6.23.31 SPC Kp TC torque
0
1000
ms
0
1297
P2.6.23.32
Flux reference
0.0
500.0
%
100.0
1250
P2.6.23.33 Speed error filter
TC
0
1000
ms
0
1311
VACON · 174
MULTI-PURPOSE CONTROL APPLICATION
6