Table 7: Output signals, G2.3
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.7
Digital output 1
function
0
16
1
312
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = FC overheat
warning
6 = Ext. fault or
warning
7 = Ref. fault or
warning
8 = Warning
9 = Reversed
10 = Preset speed
1
11 = At speed
12 = Mot. regulator
active
13 = OP freq. limit
1 superv.
14 = Control place:
IO
15 = Therminstor
fault/warning
16 = Fieldbus DIN1
P2.3.8
RO1 function
0
16
2
313
As parameter 2.3.7
P2.3.9
RO2 function
0
16
3
314
As parameter 2.3.7
P2.3.10
Output frequency
limit 1 supervision
0
2
0
315
0 = No limit
1 = Low limit
supervision
2 = High limit
supervision
P2.3.11
Output frequency
limit 1; Supervised
value
0.00
320.00
Hz
0.00
316
P2.3.12 * Analogue output 2
signal selection
0.1
E.10
0.1
471
TTF programming
method used. See
P2.3.13
Analogue output 2
function
0
8
4
472
As parameter 2.3.2
P2.3.14
Analogue output 2
filter time
0.00
10.00
s
1.00
473
0 = No filtering
VACON · 30
STANDARD APPLICATION
2
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205