Table 65: Limit settings (Control keypad: Menu M2 -> G2.3.4)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.4.9
External brake-off
delay
0.0
100.0
s
0.5
352
From brake-off
limits.
P2.3.4.10 External brake-on
delay
0.0
100.0
s
1.5
353
From Run request.
Use time longer
than P2.1.4.
P2.3.4.11 Temperature limit
supervision
0
2
0
354
0 = No supervision
1 = Low limit
2 = High limit
P2.3.4.12
Temperature
supervised value
-10
100
°C
40
355
P2.3.4.13 Analogue supervi-
sion signal
0
4
0
356
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
P2.3.4.14 Analogue supervi-
sion low limit
0.00
100.00
%
10.00
357
DO Off limit. See
P2.3.3.22.
P2.3.4.15 Analogue supervi-
sion high limit
0.00
100.00
%
90.00
358
DO Off limit. See
P2.3.3.22.
NXP drives only
P2.3.4.16 Brake On/Off Cur-
rent Limit
0
2 x I
H
A
0
1085
Brake is closed
and kept closed if
current is below
this value.
MULTI-PURPOSE CONTROL APPLICATION
VACON · 161