1.4.2
BASIC PARAMETERS (CONTROL KEYPAD: MENU M2 -> G2.1)
Table 2: Basic parameters G2.1
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.1
Min frequency
0.00
P2.2
Hz
0.00
101
P2.2
Max frequency
P2.1
320.00
Hz
50.00
102
If f
max
> than the
motor synchro-
nous speed,
check suitability
for motor and
drive system.
P2.3
Acceleration
time 1
0.1
3000.0
s
3.0
103
Gives the time that
is necessary for
the output fre-
quency to increase
from zero fre-
quency to maxi-
mum frequency.
P2.4
Decelaration
time 1
0.1
3000.0
s
3.0
104
Gives the time that
is necessary for
the output fre-
quency to
decrease from
maximum fre-
quency to zero fre-
quency.
P2.5
Current limit
0.1 x I
H
2 x I
H
A
I
L
107
P2.6
Nominal voltage
of the motor
180
690
V
NX2:
230V
NX5:
400V
NX6:
690V
110
Find the value Un
on the rating plate
of the motor. Find
out if the motor
connection is Delta
or Star.
P2.7
Nominal fre-
quency of the
motor
8.00
320.00
Hz
50.00
111
Find the value fn
on the rating plate
of the motor.
P2.8
Nominal speed of
the motor
24
20 000
rpm
1440
112
Find the value nn
on the rating plate
of the motor.
P2.9
Nominal current
of the motor
0.1 x I
H
2 X I
H
A
I
H
113
Find the value In
on the rating plate
of the motor.
BASIC APPLICATION
VACON · 15
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
1
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......