Table 186: Selections for parameter ID740
Selection
number
Selection name
Description
0
No response
1
Warning
2
Fault, stop mode after fault
according to ID506
3
Fault, stop mode after fault
always by coasting
741 TBOARD1 WARN.LIM (PT100 WARNING LIMIT) 567 (2.7.26)
NOTE!
The parameter name TBoard1 Warn.Lim is used in Multi-Purpose Control
Application. The old name (PT100 warning limit) is still used in PID Control
Application and Pump and Fan Control Application.
Set here the limit at which the temperature warning will be activated.
742 TBOARD1 FLT.LIM (PT100 FAULT LIMIT) 567 (2.7.27)
NOTE!
The parameter name TBoard1 Flt.Lim is used in Multi-Purpose Control Application.
The old name (PT100 fault limit) is still used in PID Control Application and Pump
and Fan Control Application.
Set here the limit at which the temperature fault (F56) will be activated.
743 TBOARD2 NUMBERS 6 (2.7.37)
If you have a temperature board installed in your AC drive you can choose here the number
of sensors in use. See also the Vacon I/O boards manual.
VACON · 334
PARAMETER DESCRIPTIONS
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205