Table 87: Analogue input 1 (Control keypad: Menu M2 -> G2.2.2)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.2.1
**
AI1 signal selec-
tion
0.1
E.10
A.1
377
TTF programming.
See Chapter 8.9
P2.2.2.2
AI1 filter time
0.00
10.00
s
0.10
324
0 = No filtering
P2.2.2.3
AI1 signal range
0
2
0
320
0 = 0-10 V (0-20
mA*)
1 = 2-10 V (4-20
mA*)
2 = Customised *
P2.2.2.4
AI1 custom mini-
mum setting
-160.00
160.00
%
0.00
321
P2.2.2.5
AI1 custom maxi-
mum setting
-160.00
160.00
%
100.00
322
P2.2.2.6
AI1 signal inver-
sion
0
1
0
323
0 = Not inverted
1 = Inverted
* = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
** = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle)