Table 93: Limit settings (Control keypad: Menu M2 -> G2.3.2)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.2.1
Output frequency
limit 1 supervision
0
2
0
315
0 = No limit
1 = Low limit
supervision
2 = High limit
supervision
P2.3.2.2
Output frequency
limit 1; Supervised
value
0.00
320.00
Hz
0.00
316
P2.3.2.3
Output frequency
limit 2 supervision
0
2
0
346
0 = No limit
1 = Low limit
supervision
2 = High limit
supervision
P2.3.2.4
Output frequency
limit 2; Supervised
value
0.00
320.00
Hz
0.00
347
P2.3.2.5
Torque limit
supervision
0
2
0
348
0 = Not used
1 = Low limit
supervision
2 = High limit
supervision
P2.3.2.6
Torque limit
supervision value
-300.0
300.0
%
100.0
349
Absolute values
are used for brake
control.
P2.3.2.7
Reference limit
supervision
0
2
0
350
0 = Not used
1 = Low limit
2 = High limit
P2.3.2.8
Reference limit
supervision value
0.0
100.0
%
0.0
351
P2.3.2.9
External brake-off
delay
0.0
100.0
s
0.5
352
From brake-off
limits
P2.3.2.10 External brake-on
delay
0.0
100.0
s
1.5
353
From Run request.
Use time longer
than P2.1.4.
P2.3.2.11
FC temperature
supervision
0
2
0
354
0 = Not used
1 = Low limit
2 = High limit
PUMP AND FAN CONTROL APPLICATION
VACON · 217
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
7