6.4.5
DRIVE CONTROL PARAMETERS (CONTROL KEYPAD: MENU M2 -> G2.4
Table 69: Drive control parameters, G2.4
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.4.1
Ramp 1 shape
0.0
10.0
s
0.1
500
0 = Linear
100 = Full acc/dec
inc/dec times
P2.4.2
Ramp 2 shape
0.0
10.0
s
0.0
501
0 = Linear
100 = Full acc/dec
inc/dec times
P2.4.3
Acceleration time
2
0.1
3000.0
s
10.0
502
Defines the time
that is necessary
for the output fre-
quency to increase
from zero fre-
quency to maxi-
mum frequency.
P2.4.4
Deceleration time
2
0.1
3000.0
s
10.0
503
Defines the time
that is necessary
for the output fre-
quency to
decrease from
maximum fre-
quency to zero fre-
quency.
P2.4.5 *
Brake chopper
0
4
0
504
0 = Disabled
1 = Used when
running
2 = External brake
chopper
3 = Used when
stopped/running
4 = used when
running (no test-
ing)
P2.4.6
Start function
0
2
0
505
0 = Ramp
1 = Flying start
2 = Conditional fly-
ing start
MULTI-PURPOSE CONTROL APPLICATION