Table 77: Stabilators
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.6.26.1
Torque stabilator
gain
0
1000
100
1412
The gain of the tor-
que stabilator in an
open loop control
operation.
P2.6.26.2
Torque stabilator
damping
0
1000
900
1413
The damping time
constant of the tor-
que stabilator. For
PMSM, use value
980.
P2.6.26.3
Torque stabilator
gain FWP
0
1000
50
1414
The gain of the tor-
que stabilator at
field weakening
point in an open
loop control opera-
tion.
P2.6.26.4
Torque stabilator
limit ratio
0
20.00
%
3.00
1720
Defines how much
the torque stabil-
iser can affect the
output frequency.
P2.6.26.5
Flux circle stabi-
lator gain
0
32767
10000
1550
Gain for flux circle
stabilizer.
P2.6.26.6
Flux stabilator TC
0
32700
900
1551
Filter coefficient of
idcurrent stabil-
izer.
P2.6.26.7
Flux stabilator
gain
0
32000
500
1797
Gain of flux stabil-
izer.
P2.6.26.8
Flux stabilator
coefficient
-30000
32766
64
1796
Filter coefficient of
flux stabilizer,
32767 equals 1 ms.
P2.6.26.9
Voltage stabilator
gain
0
100.0
%
10.0
1738
Gain of voltage
stabilizer.
P2.6.26.10 Voltage stabilator
TC
0
1000
900
1552
Damping rate of
voltage stabilizer.
P2.6.26.11 Voltage stabilator
limit
0
32000
Hz
1.50
1553
Limit of torque
stabilator output
Limit[Hz]= Value/
FreqScale.
VACON · 180
MULTI-PURPOSE CONTROL APPLICATION
6
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205