44 Hz
40 Hz
36 Hz
f/Hz
Adjusted
AI
Adjust 0%
Adjust maximum
ID495 = 10%
Adjust minimum
ID494 = 10%
Fig. 66: An example of adjust input
494 ADJUST MINIMUM 6 (2.2.1.5)
495 ADJUST MAXIMUM 6 (2.2.1.6)
These parameters define the minimum and maximum of adjusted signals. See Fig. 66 An
NOTE!
The adjustment is made to the basic reference signal.
496 PARAMETER SET 1/SET 2 SELECTION * 6 (2.2.7.21)
This parameter defines the digital input, which can be used to select between Parameter Set
1 and Set 2. The input for this function can be selected from any slot. The procedure of
selecting between the sets is explained in the product's User Manual.
Digital input = FALSE:
-
Set 1 is loaded as the active set
Digital input = TRUE:
-
Set 2 is loaded as the active set
NOTE!
The parameter values are stored only when selecting P6.3.1 Parameter sets Store
Set 1 or Store Set 2 in System menu or from NCDrive: Drive > Parameter Sets.