Table 17: Output signals, G2.3
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.7
Digital output 1
function
0
22
1
312
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = FC overheat
warning
6 = Ext. fault or
warning
7 = Ref. fault or
warning
8 = Warning
9 = Reversed
10 = Jogging spd
selected
11 = At speed
12 = Mot. regulator
active
13 = OP freq. limit
superv. 1
14 = OP freq. limit
superv.2
15 = Torque limit
superv.
16 = Ref. limit
superv.
17 = Ext. brake
control
18 = Control place:
IO
19 = FC temp. limit
superv.
20 = Unrequested
rotation direction
21 = Ext. brake
control inverted
22 = Thermistor
fault/warn.
P2.3.8
RO1 function
0
22
2
313
As parameter 2.3.7
P2.3.9
RO2 function
0
22
3
314
As parameter 2.3.7
P2.3.10
Output frequency
limit 1 supervision
0
2
0
315
0 = No limit
1 = Low limit
supervision
2 = High limit
supervision
P2.3.11
Output frequency
limit 1; Supervised
value
0.00
320.00
Hz
0.00
316
VACON · 56
LOCAL/REMOTE CONTROL APPLICATION
3
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......