Table 131: Selections for parameter ID343
Selection
number
Selection name
Description
0
AI1 reference
(terminals 2 and 3, e.g. potentiometer)
1
AI2 reference
(terminals 5 and 6, e.g. transducer)
2
AI3 reference
3
AI4 reference
4
Keypad reference (parameter
R3.2)
5
Reference from Fieldbus
(FBSpeedReference)
6
Motor potentiometer reference
7
PID controller reference
Select actual value (parameter ID333 to ID339) and the PID control reference (parameter
ID332). If value 6 is selected for this parameter in Application 5, the values of parameters
ID319 and ID301 are automatically set to 13.
In Application 7, the functions Motorpotentiometer DOWN and Motorpotentiometer UP must
be connected to digital inputs (parameters ID417 and ID418), if value 6 is selected for this
parameter.
344 REFERENCE SCALING MINIMUM VALUE, PLACE B 57 (2.2.35, 2.2.1.18)
345 REFERENCE SCALING MAXIMUM VALUE, PLACE B 57 (2.2.36, 2.2.1.19)
You can choose a scaling range for the frequency reference from control place B between
the Minimum and Maximum frequency.
If no scaling is desired set the parameter value to 0.
In figures below, input AI1 with signal range 0-100% is selected for Place B reference.
NOTE!
This scaling does not affect the fieldbus reference (scaled between Minimum
frequency (parameter ID101) and Maximum frequency (parameter ID102).
VACON · 272
PARAMETER DESCRIPTIONS
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......