Table 85: Basic parameters G2.1
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.1.10 *
Motor cos phi
0.30
1.00
0.85
120
Find the value on
the rating plate of
the motor.
P2.1.11 *
PID controller ref-
erence signal
(Place A)
0
6
4
332
0 = AI1
1 = AI2
2 = AI3
3 = AI4
4 = PID ref from
Keypad control
page, P3.4
5 = PID ref. from
fieldbus (FBPro-
cessDataIN1)
6 = Motor potenti-
ometer
P2.1.12
PID controller
gain
0.0
1000.0
%
100.0
118
If the value of the
parameter is set to
100%, a change of
10% in the error
value causes the
controller output
to change by 10%.
P2.1.13
PID controller I-
time
0.00
320.00
s
1.00
119
If this parameter is
set to 1.00 s, a
change of 10% in
the error value
causes the con-
troller output to
change by
10.00%/s.
P2.1.14
PID controller D-
time
0.00
10.00
s
0.00
132
If this parameter is
set to 1.00 s, a
change of 10% in
the error value
during 1.00 s cau-
ses the controller
output to change
by 10.00%.
P2.1.15
Sleep frequency
0
P2.1.2
Hz
10.00
1016
The drive goes to
sleep mode when
the output fre-
quency stays below
this limit for a lon-
ger time than set
by Sleep Delay.
VACON · 204
PUMP AND FAN CONTROL APPLICATION
7
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......