Table 89: Analogue input 3 (Control keypad: Menu M2 -> G2.2.4)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.4.1
**
AI3 signal selec-
tion
0.1
E.10
0.1
141
TTF programming.
See Chapter 8.9
P2.2.4.2
AI3 filter time
0.00
10.00
s
0.10
142
0 = No filtering
P2.2.4.3
AI3 signal range
0
2
1
143
0 = 0-10 V
(0-20mA*)
1 = 2-10 V (4-20
mA*)
1 = Customised *
P2.2.4.4
AI3 custom mini-
mum setting
-160.00
160.00
%
0.00
144
% of input signal
range. e.g. 2 mA =
10 %
P2.2.4.5
AI3 custom maxi-
mum setting
-160.00
160.00
%
100.00
145
e.g. 18 mA = 90 %
P2.2.4.6
AI3 signal inver-
sion
0
1
0
151
0 = Not inverted
1 = Inverted
* = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
** = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle)
PUMP AND FAN CONTROL APPLICATION
VACON · 211