8.10
SPEED CONTROL PARAMETERS (APPLICATION 6 ONLY)
FieldWeakeningPoint
W SpeedControl_Kp_FW
W SpeedControl_Kp_f0
W SpeedControl_f0
W SpeedControl_f1
W
Gain -%
f
100 %
Fig. 96: Speed Controller adaptive gain
1295 SPEED CONTROLLER TORQUE MINIMUM GAIN 6 (2.6.23.30)
The relative gain as a percentage of ID613 of the speed controller when the torque reference
or the speed control output is less than the value of parameter ID1296. This parameter is
normally used to stabilise the speed controller for a drive system with gear backlash.
1296 SPEED CONTROLLER TORQUE MINIMUM 6 (2.6.23.29)
The level of torque reference below which the speed controller gain is changed from ID613 to
ID1295 . This is in percentage of motor nominal torque. The change is filtered according to
parameter ID1297.
1297 SPEED CONTROLLER TORQUE MINIMUM FILTERING TIME 6 (2.6.23.31)
Filtering time for torque when the speed controller gain is changed between ID613 and
ID1295 depending on ID1296.
1298 SPEED CONTROLLER GAIN IN FIELD WEAKENING AREA 6 (2.6.23.28)
The relative gain of the speed controller in the field weakening area as a percentage of
parameter ID613.
1299 SPEED CONTROLLER GAIN F0 6 (2.6.23.27)
The relative gain of the speed controller as a percentage of parameter ID613 when the speed
is below the level defined by ID1300.
1300 SPEED CONTROLLER F0 POINT 6 (2.6.23.26)
The speed level in Hz below which the speed controller gain is equal to parameter ID1299.
PARAMETER DESCRIPTIONS
VACON · 377
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]