Table 74: NXP drives: PMS Motor control parameters (Control keypad: Menu M2 -> G2.6.24)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.6.24.1
Motor type
0
1
0
650
0 = Induction
Motor
1 = PMS Motor
P2.6.24.2
PMSMShaft posi-
tion
0
65535
0
649
Low word of
encoder (endat)
angle correspond-
ing to the shaft 0
position.
P2.6.24.3
Start angle ID
modified
0
10
0
1691
P2.6.24.4 Start Angle ID cur-
rent
0.0
150.0
%
0.0
1756
Shaft angle identi-
fication current
level 1000 =
100.0% of motor
nominal.
P2.6.24.5 Polarity pulse cur-
rent
-1.0
200.0
%
-1.0
1566
Shaft angle identi-
fication polarity
pulse current level
1000 = 100.0% of
motor nominal (0 =
defaults are used,
negative value dis-
ables polarity pul-
ses).
P2.6.24.6
I/f current
0.0
150.0
%
50.0
1693
Dc-current level
during the start
positioning,
0-100.0% of nomi-
nal, PMSM.
P2.6.24.7
I/f control limit
0.0
300.0
%
10.0
1790
Second corner
frquency (mixed
current/voltage
mode frequency)
(0-1000) = 0-100%
of MotorNomFreq.
P2.6.24.8
FluxCurrent Kp
0
32000
500
651
P2.6.24.9
FluxCurrent Time
0.0
100.0
ms
5.0
652
VACON · 176
MULTI-PURPOSE CONTROL APPLICATION
6
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205