Table 64: Digital ouput signals (Control keypad: Menu M2 -> G2.2.4)
Index
Parameter
Min
Default
Cust
ID
Description
P2.3.3.1 *
Ready
0.1
A.1
432
Ready to Run
P2.3.3.2 *
Run
0.1
B.1
433
Running
P2.3.3.3 *
Fault
0.1
B.2
434
Drive in fault state
P2.3.3.4 *
Inverted fault
0.1
0.1
435
Drive not in fault state
P2.3.3.5 *
Warning
0.1
0.1
436
Warning active
P2.3.3.6 *
External fault
0.1
0.1
437
External fault active
P2.3.3.7 *
Reference fault/warning
0.1
0.1
438
4 mA fault or warning active
P2.3.3.8 *
Overtemperature warning
0.1
0.1
439
Drive overtemperature active
P2.3.3.9 *
Reverse
0.1
0.1
440
Output frequency < 0 Hz
P2.3.3.10 *
Unrequested direction
0.1
0.1
441
Actual direction <> reques-
ted direction
P2.3.3.11 *
At speed
0.1
0.1
442
Reference = Output fre-
quency
P2.3.3.12 *
Jogging speed
0.1
0.1
443
Jogging or preset speed
command active
P2.3.3.13 *
I/O control place
0.1
0.1
444
IO control active
P2.3.3.14 *
External brake control
0.1
0.1
445
See IDs 445 and 446 in Chap-
P2.3.3.15 *
External brake control,
inverted
0.1
0.1
446
P2.3.3.16 *
Output frequency limit 1
supervision
0.1
0.1
447
See ID315 in Chapter 8
P2.3.3.17 *
Output frequency limit 2
supervision
0.1
0.1
448
See ID346 in Chapter 8
P2.3.3.18 * Reference limit supervision
0.1
0.1
449
See ID350 in Chapter 8
P2.3.3.19 * Temperature limit supervi-
sion
0.1
0.1
450
Drive temperature supervi-
sion. See ID354 in Chapter 8
P2.3.3.20 *
Torque limit supervision
0.1
0.1
451
See ID348 in Chapter 8
P2.3.3.21 *
Themistor fault or warning
0.1
0.1
452
P2.3.3.22 * Analogue input supervision
limit
0.1
0.1
463
See ID356 in Chapter 8
VACON · 158
MULTI-PURPOSE CONTROL APPLICATION
6
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......