Table 18: Drive control parameters, G2.4
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.4.9
DC braking time
at stop
0.00
600.00
s
0.00
508
0 = DC brake is off
at stop
P2.4.10
Frequency to start
DC braking during
ramp stop
0.10
10.00
Hz
1.50
515
P2.4.11
DC braking time
at start
0.00
600.00
s
0.00
516
0 = DC brake is off
at start
P2.4.12 *
Flux brake
0
1
0
520
0 = Off
0 = On
P2.4.13
Flux braking cur-
rent
0.00
I
L
A
I
H
519
3.4.6
PROHIBIT FREQUENCY PARAMETERS (CONTROL KEYPAD: MENU M2 -> G2.5)
Table 19: Prohibit frequency parameters, G2.5
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.5.1
Prohibit frequency
range 1 low limit
0.00
320.00
Hz
0.00
509
P2.5.2
Prohibit frequency
range 1 high limit
0.00
320.00
Hz
0.00
510
0 = Prohibit range
1 is off
P2.5.3
Prohibit frequency
range 2 low limit
0.00
320.00
Hz
0.00
511
P2.5.4
Prohibit frequency
range 2 high limit
0.00
320.00
Hz
0.00
512
0 = Prohibit range
2 is off
P2.5.5
Prohibit frequency
range 3 low limit
0.00
320.00
Hz
0.00
513
P2.5.6
Prohibit frequency
range 3 high limit
0.00
320.00
Hz
0.00
514
0 = Prohibit range
3 is off
P2.5.7
Prohibit acc./dec.
ramp
0.1
10.0
x
1.0
518
VACON · 60
LOCAL/REMOTE CONTROL APPLICATION
3
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......