Table 57: Analogue input 2 (Control keypad: Menu M2 -> G2.2.3)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.3.1
**
AI2 signal selec-
tion
0.1
E.10
A.2
388
TTF programming.
See Chapter 8.9
P2.2.3.2
AI2 filter time
0.00
320.00
s
0.10
329
0 = No filtering
P2.2.3.3
AI2 signal range
0
3
1
325
0 = 0-10 V
(0-20mA*)
1 = 2-10 V (4-20
mA*)
2 = -10V...+10 V*
3 = Custom range
*
P2.2.3.4
AI2 custom mini-
mum setting
-160.00
160.00
%
20.00
326
The percentage of
input signal range.
For example, 2 mA
= 10%
P2.2.3.5
AI2 custom maxi-
mum setting
-160.00
160.00
%
100.00
327
For example 18
mA = 90%
P2.2.3.6
AI2 reference
scaling, minimum
value
0.00
320.00
Hz
0.00
393
Selects the fre-
quency that corre-
sponds to the min.
reference signal.
P2.2.3.7
AI2 reference
scaling, maximum
value
0.00
320.00
Hz
0.00
394
Selects the fre-
quency that corre-
sponds to the max.
reference signal.
P2.2.3.8
AI2 joystick hyste-
resis
0.00
20.00
%
0.00
395
When the refer-
ence is between 0
and 0 ± this
parameter, the
reference is set to
0.
P2.2.3.9
AI2 sleep limit
0.00
100.00
%
0.00
396
The AC drive goes
to sleep mode if
input is below this
limit for set time.
P2.2.3.10
AI2 sleep delay
0.00
320.00
s
0.00
397
P2.2.3.11
AI2 joystick offset
-100.00
100.00
%
0.00
166
Press 'Enter' for 1s
to set offset,
'Reset' to set 0.00.
* = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
MULTI-PURPOSE CONTROL APPLICATION
VACON · 149
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
6
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......