Table 84: Monitoring values
Index
Monitoring value
Unit
ID
Description
V1.1
Output frequency
Hz
1
The output frequency to motor
V1.2
Frequency reference
Hz
25
The frequency reference to motor control
V1.3
Motor speed
rpm
2
The actual speed of the motor in rpm
V1.4
Motor current
A
3
V1.5
Motor torque
%
4
The calculated shaft torque
V1.6
Motor power
%
5
The calculated motor shaft power in percentage
V1.7
Motor voltage
V
6
The output voltage to motor
V1.8
DC link voltage
V
7
The measured voltage in the DC-link of the drive
1.9
Unit temperature
°C
8
The heatsink temperature in Celsius or Fahrenheit
1.10
Motor temperature
%
9
The calculated motor temperature in percentage
of the nominal working temperature
V1.11
Analogue input 1
V/mA
13
AI1
V1.12
Analogue input 2
V/mA
14
AI2
V1.13
DIN 1, 2, 3
15
Shows the status of the digital inputs 1-3
V1.14
DIN 4, 5, 6
16
Shows the status of the digital inputs 4-6
V1.15
Analogue I
out
mA
26
AO1
V1.16
Analogue input 3
V/mA
27
AI3 input value
V1.17
Analogue input 4
V/mA
28
AI4 input value
V1.18
PID Reference
%
20
In % of the max. frequency
V1.19
PID Actual value
%
21
In % of the max actual value
V1.20
PID Error value
%
22
In % of the max error value
V1.21
PID Output
%
23
In % of the max output value
V1.22
Running auxiliary
drives
30
Number of running auxiliary drives
V1.23
Special display for
actual value
29
See parameters 2.9.29 to 2.9.31
V1.24
PT-100 temperature
ºC
42
Highest temperature of used PT100 inputs
G1.25
Multimonitoring
items
Displays three selectable monitoring values
PUMP AND FAN CONTROL APPLICATION
VACON · 201
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]