Table 127: Selection for parameter ID332
Applic.
5
7
Sel.
0
Analogue input 1
Analogue input 1
1
Analogue input 2
Analogue input 2
2
PID ref. from menu M3, parameter P3.4
AI3
3
Fieldbus ref. (FBProcessDataIN1) See Chap-
ter 8.7 Fieldbus control parameters (IDs 850 to
AI4
4
Motor potentiometer reference
PID ref. from menu M3, parameter P3.4
5
Fieldbus ref. (FBProcessDataIN1) See Chapter
8.7 Fieldbus control parameters (IDs 850 to 859).
6
Motor potentiometer reference
333 PID CONTROLLER ACTUAL VALUE SELECTION 57 (2.2.8, 2.2.1.8)
This parameter selects the PID controller actual value.
Table 128: Selections for parameter ID333
Selection
number
Selection name
Description
0
Actual value 1
1
Actual value 1 + Actual value 2
2
Actual value 1 – Actual value 2
3
Actual value 1 * Actual value 2
4
Smaller one of Actual value 1
and Actual value 2
5
Greater one of Actual value 1
and Actual value 2
6
Mean value of Actual value 1
and Actual value 2
7
Square root of Actual value 1 +
Square root of Actual value 2
334 ACTUAL VALUE 1 SELECTION 57 (2.2.9, 2.2.1.9)
PARAMETER DESCRIPTIONS
VACON · 269
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
8
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......