6.4.9
AUTORESTART PARAMETERS (CONTROL KEYPAD: MENU M2 -> G2.8)
Table 79: Autorestart parameters, G2.8
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.8.1
Wait time
0.10
10.00
s
0.50
717
The wait time
before the first
reset is done.
P2.8.2
Trial time
0.00
60.00
s
30.00
718
When the trial time
is over, and the
fault is still active,
the drive will trip.
P2.8.3
Start function
0
2
0
719
The selection of
the start mode for
Automatic reset.
0 = Ramp
1 = Flying start
2 = According to
P2.4.6
P2.8.4
Number of tries
after undervoltage
trip
0
10
0
720
P2.8.5
Number of tries
after overvoltage
trip
0
10
0
721
P2.8.6
Number of tries
after overcurrent
trip
0
3
0
722
P2.8.7
Number of tries
after 4mA refer-
ence trip
0
10
0
723
P2.8.8
Number of tries
after motor tem-
perature fault trip
0
10
0
726
P2.8.9
Number of tries
after external
fault trip
0
10
0
725
P2.8.10
Number of tries
after underload
fault trip
0
10
0
738
VACON · 186
MULTI-PURPOSE CONTROL APPLICATION
6