Table 164: Selections for parameter ID644
Selection
number
Selection name
Description
0
Maximum frequency
1
Selected frequency reference
2
Preset speed 7
NXP drives have more selections for this parameter in Closed Loop control mode. See
ID1278.
645 NEGATIVE TORQUE LIMIT 6 (2.6.23.21)
646 POSITIVE TORQUE LIMIT 6 (2.6.23.22)
Defines the torque limit for positive and negative directions.
649 PMS MOTOR ZERO SHAFT POSITION 6 (2.6.24.4)
Identified zero shaft position. Updated during encoder identification run with an absolute
encoder.
650 MOTOR TYPE 6 (2.6.24.1)
In this parameter, you can set the type of motor in your process.
Table 165: Selections for ID650
Selection
number
Selection name
Description
0
Induction motor
1
Permanent magnet synchro-
nous motor
654 ENABLE RS IDENTIFICATION 6 (2.6.24.5)
With this parameter its possible to disable Rs identification during DC brake start. The
parameter default value is 1 (Yes).
655 MODULATION LIMIT 6 (2.6.23.34)
This parameter can be used to control how the drive modulates the output voltage. Reducing
this value limits the maximum output voltage. If a sinusoidal filter is used set this parameter
to 96%.
VACON · 318
PARAMETER DESCRIPTIONS
8