Table 175: Selections for parameter ID721
Selection
number
Selection name
Description
0
No automatic restart after
overvoltage fault trip
>0
Number of automatic restarts
after overvoltage fault trip.
The fault is reset and the drive is started automatically after
the DC-link voltage has returned to the normal level.
722 AUTOMATIC RESTART: NUMBER OF TRIES AFTER OVERCURRENT TRIP 234567 (2.8.6)
NOTE!
IGBT temp fault also included.
This parameter determines how many automatics restarts can be made during the trial time
set by ID718.
Table 176: Selections for parameter ID722
Selection
number
Selection name
Description
0
No automatic restart after
overcurrent fault trip
>0
Number of automatic restarts
after overcurrent trip and IGBT
temperature faults.
723 AUTOMATIC RESTART: NUMBER OF TRIES AFTER 4MA REFERENCE TRIP 234567 (2.8.7)
This parameter determines how many automatics restarts can be made during the trial time
set by ID718.
Table 177: Selections for parameter ID 723
Selection
number
Selection name
Description
0
No automatic restart after ref-
erence fault trip
>0
Number of automatic restarts
after the analogue current sig-
nal (4-20mA) has returned to
the normal level (>4mA)
PARAMETER DESCRIPTIONS
VACON · 329
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
8