119 PID CONTROLLER I-TIME 57 (2.1.13)
The parameter ID119 defines the integration time of the PID controller. If this parameter is
set to 1.00 s, a change of 10% in the error value causes the controller output to change by
10.00%/s. If the parameter value is set to 0.00 s, the PID controller will operate as PD
controller.
For examples, see ID132.
120 MOTOR COS PHI (2.10, 2.1.10)
Find this value on the rating plate of the motor.
121 KEYPAD FREQUENCY REFERENCE SELECTION 234567 (2.1.12, 2.1.13, 2.2.6, 2.2.1.2)
Selection of the reference source when the control place is keypad.
Table 107: Selection for parameter ID121
Appl.
2-4
5
6
7
Sel.
0
Analogue input 1 (AI1)
Analogue input 1 (AI1)
Analogue input 1 (AI1)
Analogue input 1 (AI1
1
Analogue Input 2 (AI2)
Analogue Input 2 (AI2)
Analogue Input 2 (AI2)
Analogue Input 2 (AI2)
2
Keypad reference
(Menu M3)
AI3
AI1+AI2
AI3
3
Fieldbus reference*
AI4
AI1–AI2
AI4
4
Keypad reference (Menu
M3)
AI2–AI1
Keypad reference
(Menu M3)
5
Fieldbus reference*
AI1*AI2
Fieldbus reference*
6
Potentiometer ref.
AI1 joystick
Potentiometer ref.
7
PID controller ref.
AI2 joystick
PID controller ref.
8
Keypad reference
(Menu M3)
9
Fieldbus reference*
*FBSpeedReference. For more information, see the used fieldbus manual.
122 FIELDBUS FREQUENCY REFERENCE SELECTION 234567 (2.1.13, 2.1.14, 2.2.7, 2.2.1.3)
Selection of the reference source when the control place is Fieldbus.
For selections in different applications, see ID121.
PARAMETER DESCRIPTIONS
VACON · 241
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
8
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......