Table 73: NXP drives: Closed Loop parameters (Control keypad: Menu M2 ->G2.6.23)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.6.23.1
Magnetizing cur-
rent
0.00
2 x I
H
A
0.00
612
If zero internally
calculated.
P2.6.23.2
Speed control P
1
1000
30
613
P2.6.23.3
Speed control I
time
-32000
3200.0
ms
100.0
614
Negative value
uses 1 ms accu-
racy instead of 0.1
ms.
P2.6.23.5
Acceleration
compensation
0.00
300.00
s
0.00
626
P2.6.23.6
Slip adjust
0
500
%
75
619
P2.6.23.7
Magnetizing cur-
rent at start
0
I
L
A
0.00
627
P2.6.23.8
Magnetizing time
at start
0
60000
ms
0
628
P2.6.23.9
0-speed time at
start
0
32000
ms
100
615
P2.6.23.10
0-speed time at
stop
0
32000
ms
100
616
P2.6.23.11
Start-up torque
0
3
0
621
0 = Not used
1 = Torque mem-
ory
2 = Torque refer-
ence
3 = Start-up torque
fwd/rev
P2.6.23.12
Start-up torque
FWD
-300.0
300.0
s
0.0
633
P2.6.23.13
Start-up torque
REV
-300.0
300.0
s
0.0
634
P2.6.23.15
Encoder filter
time
0.0
100.0
ms
0.0
618
MULTI-PURPOSE CONTROL APPLICATION
VACON · 173
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
6
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......