Table 124: Selections for parameter ID319
Selection
number
Selection name
Description
Notes
1
External fault,
normally open
Contact closed: Fault is displayed and motor
stopped when the input is active
2
External fault,
normally closed
Contact open: Fault is displayed and motor
stopped when the input is not active.
3
Run enable
Contact open, Start of motor disabled.
Contact closed: Start of motor enabled
4
Acceleration or
deceleration time
selection
Contact open, Acceleration/Deceleration time
1 selected
Contact closed: Acceleration/Deceleration
time 2 selected
5
Closing contact
Force control place to I/O terminal
When the control place is
forced to change the values
of Start/Stop, Direction and
Reference valid in the
respective control place are
used (reference according to
parameters ID343, ID121 and
ID122).
NOTE!
The value of ID125 (Keypad
Control Place) does not
change.
When DIN2 opens the control
place is selected according
to keypad control place
selection.
6
Closing contact
Force control place to keypad
7
Closing contact
Force control place to fieldbus
8
Reverse
Contact open:Forward
If several inputs are pro-
grammed to reverse, one
active contact is enough to
set the direction to reverse.
Contact closed:Reverse
9
Jogging speed
(see par. ID124)
Contact closed: Jogging speed selected for
frequency reference
10
Fault reset
Contact closed: Resets all faults
11
Acceleration/
Deceleration pro-
hibited
Contact closed: No acceleration or decelera-
tion possible until the contact is opened
12
DC-braking com-
mand
Contact closed: In Stop mode, the DC braking
operates until the contact is opened. See Fig.
41 DC braking command (selection 12) selected
VACON · 264
PARAMETER DESCRIPTIONS
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......