Table 124: Selections for parameter ID319
Selection
number
Selection name
Description
Notes
13
Motor potentiom-
eter UP
Contact closed: Reference increases until the
contact is opened.
A
B
t
t
ID515
DIN2
f
out
f
out
RUN
STOP
DIN2
RUN
STOP
Fig. 41: DC braking command (selection 12) selected for DIN2
A. Stop mode = Ramp
B. Stop mode = Coasting
320 AI1 SIGNAL RANGE 34567 (2.2.4, 2.2.16, 2.2.2.3
Table 125: Selections for parameter ID320
Applic.
3, 4, 5
6
7
Sel.
0
0-100%
0-100%
0-100%
1
4 mA/20-100%
4 mA/20-100%
4 mA/20-100%
2
Customised
–10…+10 V
Customised
3
Customised
For selection 'Customised', see parameters ID321 and ID322.
321 AI1 CUSTOM SETTING MINIMUM 34567 (2.2.5, 2.2.17, 2.2.2.4)
322 AI1 CUSTOM SETTING MAXIMUM 34567 (2.2.6, 2.2.18, 2.2.2.5)
The parameters let you adjust the range of the analogue input signal between -160 and 160%
freely.
For example, you can use the analogue input signal as frequency reference, and set these 2
parameters between 40 and 80%. In these conditions, the frequency reference changes
between the Minimum frequency reference (ID101) and the Maximum frequency
reference(ID102), and the analogue input signal changes between 8 and 16 mA.
PARAMETER DESCRIPTIONS
VACON · 265
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
8
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......