130 PRESET SPEED 7 46 (2.1.21)
These parameters can be used to determine frequency references that are applied when
appropriate combinations of digital inputs are activated.
In Multi-Step Speed Application (Application 4), digital inputs DIN4, DIN5 and DIN6 are
assigned to Preset Speed functions. The combinations of these activated inputs select the
preset speed reference.
NOTE!
The use of TTF-programming method in the Multi-purpose Control Application.
Because all digital inputs are programmable you first have to assign three DINs for
the Preset Speed functions (parameters ID41, ID420 and ID421.
Table 110: Preset speeds 1 to 7
Speed
DIN4/ID419
DIN5/ID420
DIN6/ID421
Basic speed
0
0
0
Preset speed 1 (ID105)
1
0
0
Preset speed 2 (ID106)
0
1
0
Preset speed 3 (ID126)
1
1
0
Preset speed 4 (ID127)
0
0
1
Preset speed 5 (ID128)
1
0
1
Preset speed 6 (ID129)
0
1
1
Preset speed 7 (ID130)
1
1
1
See also parameters ID105 and ID106.
Parameter value is automatically limited to maximum frequency (ID102).
131 I/O FREQUENCY REFERENCE SELECTION, PLACE B3 (2.1.12)
See the values of the parameter ID117 above.
132 PID CONTROLLER D-TIME 57 (2.1.14)
The parameter ID132 defines the derivation time of the PID controller. If this parameter is set
to 1.00 second a change of 10% in the error value during 1.00 s causes the controller output
to change by 10.00%. If the parameter value is set to 0.00 s the PID controller will operate as
PI controller.
PARAMETER DESCRIPTIONS
VACON · 243
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
8
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......