Table 68: Analogue output 3 (Control keypad: Menu M2 -> G2.3.7)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.7.1 * Analogue output 3
signal selection
0.1
E.10
0.1
478
TTF programming
method used. See
P2.3.7.2
Analogue output 3
function
0
15
5
479
See P2.3.5.2
P2.3.7.3
Analogue output 3
filter time
0.00
10.00
s
1.00
480
0 = No filtering
P2.3.7.4
Analogue output 3
inversion
0
1
0
481
0 = Not inverted
1 = Inverted
P2.3.7.5
Analogue output 3
minimum
0
1
0
482
0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.7.6
Analogue output 3
scale
10
1000
%
100
483
P2.3.7.7
Analogue output 3
offset
-100.00
100.00
%
0.00
484
* = Use TTF method to program these parameters.
VACON · 164
MULTI-PURPOSE CONTROL APPLICATION
6
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......