Table 15: Basic parameters G2.1
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.1.10 *
Motor cos phi
0.30
1.00
0.85
120
Find the value on
the rating plate of
the motor.
P2.1.11 *
I/O A reference
0
4
1
117
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
4 = Motor potenti-
ometer
P2.1.12 *
I/O B reference
0
4
0
131
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
4 = Motor potenti-
ometer
P2.1.13 *
Keypad control
reference
0
3
2
121
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.1.14 *
Fieldbus control
reference
0
3
3
122
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.1.15 *
Jogging speed
reference
0.00
P2.1.2
Hz
0.00
124
* = Parameter value can only be changed after the AC drive has been stopped.