Table 6: Input signals, G2.2
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.2
DIN3 function
0
8
1
301
0 = Not used
1 = Ext. fault, closing
cont.
2 = Ext. fault, open-
ing cont.
3 = Run enable
4 = Acc./Dec. time
select.
5 = Force cp. to IO
6 = Force cp. to key-
pad
7 = Force cp. to field-
bus
8 = Reverse
P2.2.3
Analogue input 2
reference offset
0
1
1
302
0 = 0-20 mA (0-10 V)
**
1 = 4-20 mA (2-10 V)
**
P2.2.4
Reference scaling
minimum value
0.00
320.00
Hz
0.00
303
Selects the fre-
quency that corre-
sponds to the min.
reference signal 0.00
= No scaling
P2.2.5
Reference scaling
maximum value
0.00
320.00
Hz
0.00
304
Selects the fre-
quency that corre-
sponds to the max.
reference signal 0.00
= No scaling
P2.2.6
Reference inver-
sion
0
1
0
305
0 = Not inverted
1 = Inverted
P2.2.7
Reference filter
time
0.00
10.00
s
0.10
306
0 = No filtering
P2.2.8 ***
AI1 signal selec-
tion
A1
377
TTF programming
method used. See
P2.2.9 ***
AI2 signal selec-
tion
A2
388
TTF programming
method used. See
** = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
STANDARD APPLICATION
VACON · 27
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
2
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......