Table 66: Analogue output 1 (Control keypad: Menu M2 -> G2.3.5)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.5.1 * Analogue output 1
signal selection
0.1
E.10
A.1
464
TTF programming
method used. See
P2.3.5.2
Analogue output 1
function
0
15
1
307
0 = Not used (20
mA / 10 V)
1 = Output freq. (0-
f
max
)
2 = Freq. refer-
ence (0-f
max
)
3 = Motor speed
(0-Motor nominal
speed
4 = Motor current
(0-I
nMotor
)
5 = Motor torque
(0-T
nMotor
)
6 = Motor power
(0-P
nMotor
)
7 = Motor voltage
(0-U
nMotor
)
8 = DC link volt
(0-1000V)
9 = AI1
10 = AI2
11 = Output freq.
(f
min
- f
max
)
12 = Motor torque
(-2...+2xT
Nmot
)
13 = Motor power
(-2...+2xT
Nmot
)
14 = PT100 tem-
perature
15 = FB analogue
output Process-
Data4 (NXS)
P2.3.5.3
Analogue output 1
filter time
0.00
100.00
s
1.00
308
0 = No filtering
P2.3.5.4
Analogue output 1
inversion
0
1
0
309
0 = Not inverted
1 = Inverted
P2.3.5.5
Analogue output 1
minimum
0
1
0
310
0 = 0 mA (0 V)
1 = 4 mA (2 V)
VACON · 162
MULTI-PURPOSE CONTROL APPLICATION